Teleprotection equipment is one of the most important components in power systems protection, enabling fast and selective isolation of defective HV lines. The DZ8 teleprotection equipment is a basic building block of command type teleprotection system.
Main features
- Duplex transmission of up to four protective commands over analog transmission channels
- Programmable command transmission characteristics permit adaptation to any protection scheme
- Optimum Digital Signal Processing algorithms for secure and reliable operation via PLC channels with the highest possible transmission rate
- Signal boosting for full exploitation of the available transmission power for each protective command
- Redundant command input and output, preventing false operation due to single component failure
- Equipment setting and monitoring through built in MMI console or personal computer
- Loop Test - automatic or manual
- Internal real time clock (RTC) with provision for external clock synchronization
Technical data
| Modulation method | F6 (ON/OFF, frequency happing) |
| Operation mod | duplex four-wire transmission |
| Number of commands | up to 4 |
| Type of command | Transmission time (ms) | Dependability Pmc | Security Puc |
| Blocking | <17 | <10E-3 | <10E-3 |
| Permissive tripping | <17 | <10E-3 | <10E-4 |
| Direct tripping | <2 | <10 | <10 |
Applications
Teleprotection equipment is intended for transmission of up to four protective commands and can be used for permissive tripping, blocking and direct tripping.
Technical data
Extended carrier frequency range (RF range) 20kHz to 1000kHz
Number of duplex PLC channels 1, 2 or 3 (up to 6 on request)
PEP (Peak Envelope Power) 10, 20, 40 or 80W
Nominal channel bandwidth 4kHz
Useful AF bandwidth 300Hz to 3720Hz
Permissible line attenuation <52dB (10W/channel)
Synchronization yes - total ("master-slave" principle)
Applications
- Reconstruction, expansion and/or upgrading of the existing telecommunication system
- Establishing of back-up channels
- Transmission of teleprotection signals
Extended carrier frequency range (RF range) 20kHz to 1000kHz
Number of duplex PLC channels 1, 2 or 3 (up to 6 on request)
PEP (Peak Envelope Power) 10, 20, 40 or 80W
Nominal channel bandwidth 4kHz
Useful AF bandwidth 300Hz to 3720Hz
Permissible line attenuation <52dB (10W/channel)
Synchronization yes - total ("master-slave" principle)
Applications
- Reconstruction, expansion and/or upgrading of the existing telecommunication system
- Establishing of back-up channels
- Transmission of teleprotection signals